China ARM5E-630-3300 mccb electonic mccb build in LISG protection 3poles 630A Manufacturer, Manufacturers

Rated Current : 500A、630A

Number Of Poles : 3P / 4P

Rated Working Voltage : 400V/415V

Product Description

Operating Interface of the ARM6HUE Knob Controller
Series: ARW1
ARM6HUE operating interface after powered on
Key & Switch Settings
  • Key Descriptions
  • 1. Normal operation indicator light
  • 2. Pre alarm indicator light
  • 3. Overload fault indication
  • 4. Communication instructions
  • Switch Details
  • 5. Code dialing/remote control switching
  • 6. Neutral pole protection ratio
Interface & Buttons
  • Interface Structure
  • 7. Test interface
  • 8. Lock catch
  • Adjustment Panel Buttons
  • 9. Long delay current setting IR
  • 10. Long delay tripping delay tR
  • 11. Short delay tripping Isd
  • 12. Short delay tripping delay tsd
  • 13. Short circuit instantaneous Ii
  • 14. Ground fault tripping Ig
  • 15. Ground fault tripping delay tg
Indicator Light Status Definitions
Green light: Flashing indicates normal operation. If not on or constantly on, it indicates abnormal operation.
Yellow light off, red light flashing: Long delay fault.
Yellow light flashing, red light off: Overload warning (slow flashing represents greater than 90% of the long delay setting value; fast flashing represents greater than the long delay setting value).
Yellow light on, red light flashing: Short delay fault.
Yellow light on, red light on: Ground fault.
Flashing yellow light and flashing red light: Instantaneous fault.

Communication Indication: If a cabinet door unit is present, communication with it is indicated regardless of an upper computer. If no cabinet door unit exists but an upper computer is active, it indicates communication with the upper computer.
Main Performance Index of ARM6HUE Series Circuit Breaker
Model ARW1-6300
Rated current In (A) 40℃ 500A, 630A
Rated current of frame size Inm (A) 630A
Usage category Category A
Rated ultimate short-circuit breaking capacity level L M H
Number of poles (P) 3P 4P 3P 4P 3P 4P
Rated working voltage Ue (V) 400V/415V
Rated ultimate short-circuit breaking capacity Icu (kA) 85KA 150KA 200KA
Rated service short-circuit breaking capacity Ics (kA) 85KA 150KA 200KA
Rated short-time withstand current Icw (kA/1s) 8KA/1s
Rated working voltage Ue (V) 800V
Rated ultimate short-circuit breaking capacity lcu (kA) 36KA 50KA 50KA
Rated service short-circuit breaking capacity Ics (kA) 30KA 50KA 50KA
Rated short-time withstand current Icw (kA/1s) 8KA/1s
Rated insulation voltage Ui (V) 1000V
Rated impulse withstand current Uinmp (V) 8KV
Mechanical life (time) 7000
Electrical life (time) 400ln 1000
Arcing distance (mm) 0
Release type Microprocessor
Overall dimension (mm) ARW1 overall dimensions drawing W 140 185 140 185 140 185
L 125.5
H 123.5
Frequently Asked Questions (FAQ)
Q1: How do I know if the ARM6HUE knob controller is working normally?
A: A flashing green indicator light represents normal operation. If the light is completely off or constantly on without flashing, it signals an abnormal operation status.
Q2: What visual indicator points out an overload warning on the controller?
A: An overload warning is defined by a flashing yellow light accompanied by a turned-off red light. A slow flash indicates it has exceeded 90% of the long delay setting value, while a fast flash indicates it has gone beyond the configured long delay setting value.
Q3: How are short delay faults and ground faults distinguished by the indicator lights?
A: A short delay fault is indicated by a solid yellow light alongside a flashing red light. A ground fault is indicated when both the yellow light and the red light remain continuously on.
Q4: What is the rated ultimate short-circuit breaking capacity (Icu) for the ARW1-6300 model at 400V/415V?
A: Under 400V/415V conditions, the ultimate short-circuit breaking capacity (Icu) matches the selected category tier: Level L provides 85KA, Level M provides 150KA, and Level H provides 200KA.
Q5: What type of release mechanism is used in the ARW1-6300 circuit breaker?
A: The ARW1-6300 series circuit breaker is equipped with a high-performance microprocessor release type.
Q6: What is the expected mechanical and electrical life of the ARW1-6300?
A: The unit features a robust mechanical design with a durability limit of up to 7,000 operations, and an electrical life expectancy of 1,000 cycles under 400In load testing.

Related Products